Electrical Tester PCE-ITE 50
*We may have a couple of units In Stock. Kindly drop your contact details and we will get back to you shortly.
Model :Meter
Product Condition :new
Product Testing Status :
Not Applicable
Type :
Enquire
Availability :
On Enquiry
Warranty :
Description : Isolation test
Terminal voltage
Measuring range
Resolution
Accuracy
Load current
Short circuit current
125V (0 ... 10 %)
0,125 ... 4 MΩ
0.001 MΩ
± (2% + 10 digits)
1-mA @ Last 125 kΩ
<= 1-mA
4,001 ... 40 MΩ
0.01 MΩ
± (2% + 10 digits)
40,01 ... 400 MΩ
0.1 MΩ
± (4% + 5 digits)
400,1 ... 1000 MΩ
1 MΩ
± (5% + 5 digits)
250V (0 ... 10 %)
0,125 ... 4 MΩ
0.001 MΩ
± (2% + 10 digits)
1-mA @ Last 250 kΩ
<= 1-mA
4,001 ... 40 MΩ
0.01 MΩ
± (2% + 10 digits)
40,01 ... 400 MΩ
0.1 MΩ
± (3% + 2 digits)
400,1 ... 1000 MΩ
1 MΩ
± (3% + 2 digits)
500V (0 ... 10 %)
0,125 ... 4 MΩ
0.001 MΩ
± (2% + 10 digits)
1-mA @ Last 500 kΩ
<= 1-mA
4,001 ... 40 MΩ
0.01 MΩ
± (2% + 10 digits)
40,01 ... 400 MΩ
0.1 MΩ
± (3% + 2 digits)
400,1 ... 1000 MΩ
1 MΩ
± (4% + 5 digits)
1000 V (0 ... 10 %)
0,125 ... 4 MΩ
0.001 MΩ
± (3% + 10 digits)
1-mA @ Last 1 MΩ
<= 1-mA
4,001 ... 40 MΩ
0.01 MΩ
± (2% + 10 digits)
40,01 ... 400 MΩ
0.1 MΩ
± (3% + 2 digits)
400,1 ... 1000 MΩ
1 MΩ
± (4% + 5 digits)
Low Ohm
Measuring range
Resolution
Accuracy
Max. open circuit voltage
Overload protection
2,000 Ω
0.001 Ω
± (1.5% + 30 digits)
5.8V
250 Vrms
20,00 Ω
0.01 Ω
± (1.5% + 3 digits)
5.8V
250 Vrms
200,0 Ω
0.1 Ω
± (1.5% + 3 digits)
5.8V
250 Vrms
2000 Ω
1 Ω
± (1.5% + 5 digits)
5.8V
250 Vrms
Continuity tester
Measuring range
Resolution
Max. open circuit voltage
Overload protection
Short circuit current
2000 Ω
0.01 Ω
5.8V
250 Vrms
>= 200-mA
Grinding resistance
L-PE (Hi-Amp): Load current 4.0 A
Measuring range
Resolution
Accuracy
0.23 ... 9.99 Ω
0.01 Ω
± (4% + 4 digits)
10.0 ... 99.9 Ω
0.1 Ω
± (4% + 4 digits)
100 ... 999 Ω
1 Ω
± (4% + 4 digits)
L-PE (without tripping): Load current 15-mA
Measuring range
Resolution
Accuracy
0.23 ... 9.99 Ω
0.01 Ω
± (5% + 6 digits)
10.0 ... 99.9 Ω
0.1 Ω
± (5% + 6 digits)
100 ... 999 Ω
1 Ω
± (5% + 6 digits)
L-N: Load current 4.0 A
Measuring range
Resolution
Accuracy
0.23 ... 9.99 Ω
0.01 Ω
± (4% + 4 digits)
10.0 ... 99.9 Ω
0.1 Ω
± (4% + 4 digits)
100 ... 999 Ω
1 Ω
± (4% + 4 digits)
RCD Test
RCD (In)
10-mA, 30-mA, 100-mA, 300-mA, 650-mA, 1 A
Factors
x 1/2, x1, x2, x5
Accuracy of the tripping time
± (1% + 1 ms)
Signal form of the test current
Sine (AC), pulse (DC)
Tripping characteristics
G and S
Release time
0° or 180°
Voltage range
194 ... 260V AC (50/60 Hz)
Accuracy of current measurement
± (5% + 2 digits)
RCD Types Type A, Type B
Voltage measurement
Measuring range
Resolution
Accuracy
80...500 V AC/DC
1 V
± (2 % + 2 digits)
Frequency measurement
Measuring range
Resolution
Accuracy
45...65 Hz
1 Hz
±2 Hz
Grounding measurement
Measuring range
Resolution
Accuracy
0.00...99.99 Ω
0.01 Ω
± (2% + 30 digits)
100.0...999.9 Ω
0.1 Ω
± (2% + 6 digits)
1000...2000 Ω
1 Ω
± (2% + 6 digits)
General specifications
Power supply
8 x 1.2 ... 1.5V AA batteries
Operating time
ca. 15 h
Measurement category
CAT III 600V
Protection class
IP 65
Display
3.5" TFT (320 x 240 Pixel)
Operating environment
0 ... 45°C
0 ... 95% rH, non condensing
Measurements
24.2 x 10.5 x 14.5 cm
Weight
1.56 kg / 3.4 lbs